Operator's Manual: Models CB-3500 & CB-5000
4-3
Selecting a Location
Guidelines for Selecting a Location
The location you select for your furnace must allow the following:
Unobstructed, even heat distribution.
Safe, easy access for servicing.
Unobstructed passage for shop vehicles and equipment.
Proper clearances from combustibles. Verify according to your local safety codes.
Adequate combustion air per local codes.
Proper stack installation.
WARNING: Adhere to the following minimum clearances from combustible surfaces and
to provide adequate clearance for servicing (also refer to Figure 4B for visual reference); failure to main-
tain proper clearances may result in re, explosion, personal injury or death.
WARNING: National codes require
that your furnace is mounted a minimum
of eight (8) feet off the ground when installing the
furnace in a repair facility. Refer to NFPA-88B,
Standard for Repair Garages, Chapter 3, Hazards,
Sec. 3-2.3.1.
CLEARANCES FOR CB-3500/CB-5000
INSTALLATIONS
TOP (above blower) ......................... 2"
FRONT (burner) ............................... 60"
• SIDES ............................................ 24"
CHIMNEY CONNECTOR ................ 18"
• REAR ............................................ 18"
• BOTTOM .......................................... 24"
WARM AIR DUCTS within 3ft.** ....... 6"
**Where applicable
Figure 4B - Clearances from Combustibles
I88803-A
18"
60"
24"
REAR
2"
24"
MINIMUM CLEARANCES
SIDES
FRONT
CHIMNEY
18"
TOP
CONNECTOR
BOTTOM
CB-3500 / CB-5000 FURNACES