PROBLEM POSSIBLE CAUSE(S) POSSIBLE ACTION(S)
Pump will not prime and Pump
motor is running.
1. ere is a leak(s) in the suction
line.
2. e pump is not installed so it will
ll with oil during the priming
process.
3. e pump gears are dry.
4. e pump seal is damaged.
5. e ball valve is closed.
6. e canister lter is dirty.
7. e check valve is dirty.
8. e pump is damaged or worn out.
1. Follow the specications in Section
4 to make sure the suction line
is installed properly and that all
ttings are 100% airtight.
2. Make sure the pump head is lled
with oil prior to starting the pump.
See Section 5.
3. Follow the procedure in Section
5 to ll the oil line and prime the
pump.
4. With the pump not running, wipe
your nger along the bottom of the
cylinder at the pump sha. If there
is oil at the pump sha, the seal is
damaged. Replace the pump, or
replace the seal.
NOTE: Some oils will expand as
they warm up. Because there is
a check valve in the suction line,
the expanding oil may build up
pressure and damage the oil seal.
Install a mini-accumulator in the
1/8” port of the canister lter to
prevent the pressure build-up.
5. Open the ball valve on the suction
line.
6. Refer to Section 9 to clean the
canister lter.
7. Refer to Section 9 to clean the
check valve.
8. Replace the pump