Operator's Manual: Models CB-3500 & CB-5000
10-7
PROBLEM POSSIBLE CAUSE(S) POSSIBLE ACTION(S)
Pump will not prime and Pump motor is
NOT running.
1. ere is NO power on the pump
circuit from the burner.
2. e pump motor has shut o on
thermal overload
1. Start the burner and adjust the air
pressure regulator to 15 PSI. (a) If the
amber “pump” light on the burner
comes ON, the pump circuit on
the burner has activated properly.
Refer to the wiring diagram and
ladder schematic in Appendix B to
troubleshoot the pump circuit from
the burner to the pump. (b) If the
amber “pump” light on the burner
does NOT come ON, there is a
problem with pump circuit in the
burner. With the burner running,
check for power at the brown wire on
the air pressure switch. If there is NO
power at the brown wire, replace the
burner motor. If there is power at the
brown wire, replace the air sensing
switch.
2. (a) e pump motor is too hot the
internal thermal protection switch
shut the motor o. Wait for the motor
to cool down; the thermal switch will
automatically reset. Check voltage
and amperage draw of the pump
motor. Call your dealer if the problem
persists. (b) e coupling is not
adjusted properly, keeping the shas
of the motor and pump from turning
freely. Re-position the coupling so that
both shas turn freely. (c) e sha
on the motor or oil pump will not
turn freely. If you can’t turn the shas,
replace the faulty part(s).
Blower motor runs all the time. 1. Blower motor circuit is wired
incorrectly.
2. Blower relay is stuck in the closed
position
1. Refer to wiring diagram and
ladder schematic in Appendix B to
troubleshoot the blower circuit.
2. Test the blower motor contactor. If
it will not open when the power is
turned OFF, replace the contactor
Blower motor will not run. 1. e blower motor is not wired
correctly.
2. e fan / blower switch is defective.
3. e blower motor has overheated and
shut down on thermal reset.
4. Blower relay won't close
1. Check the fan motor wiring Refer
to the wiring diagram and ladder
schematic in Appendix B. Follow
the directions in Section 6 to test for
proper blower operation. If the blower
does not operate, shut OFF power to
the furnace and call your Clean Burn
dealer for service.
2. Replace the fan / blower switch.
3. e blower motor is too hot – the
internal thermal protection switch
shut the motor o. Wait for the motor
to cool down; the thermal switch will
automatically reset. Check voltage
and amperage draw of the blower
motor. Call your dealer if the problem
persists.
4. Test the blower motor contactor.
Check for proper voltage at the L1/
L2 lugs. Check the orange wire on the
coil for 110 volts. Replace if needed.